Technical Data:

Model

 

 

B40/6

B40/7

B40/8

B40/9

B40/10

B40/11

B40/12

Number of sections

 

 

6

7

8

9

10

11

12

 

 

 

 

 

 

Gas/oil

 

 

 

Net output

 

KW

80

100

120

140

160

180

200

Thermal output

 

KW

89

111

133

155

177

200

222

Efficiency at 100% load

 

%

90.0

90.0

90.2

90.3

90.3

90.5

90.6

Efficiency  at 30% load

 

%

91.0

91.3

91.5

91.8

92.0

92.2

92.4

Flue gas temperature*

 

úC

205

200

202

202

200

200

200

Flue gas side load loss

 

mbar

0.10

0.15

0.28

0.30

0.40

0.55

0.66

Water side load loss          

(At = 15k)

mbar

9

12

18

28

35

45

60

Water content

 

liters

66

76.5

87

97.5

108

118.5

129

Max. operating pressure

 

bar

5

5

5

5

5

5

5

Combustion chamber

Length

mm

565

686

807

928

1.049

1.170

1.291

 

diameter

mm

380

380

380

380

380

380

380

Burner connection

 

mm

130

130

130

130

130

130

130

Flue connection

 

mm

200

200

200

200

200

200

200

Flow/return connection

 

"G

21/2"

21/2"

21/2"

21/2"

21/2"

21/2"

21/2"

Fill/drain connection

 

"G

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

* Flue gas temperature is measured with CO˛ = 13% for fuel , 10% for gas and with 80úC boiler temperature

Control Panel

- Main switch
- Power signal lamp
- Control thermostat for 1st burner stage
- Control thermostat for 2 nd burner stage
- Manually reset safety thermostat
- Boiler thermostat
- Burner lock out signal lamp
- Pump switch
- thermostat test push - button
 

Main Technical Characteristics :

- High efficiency boiler
- long - lasting GG20 cast-iron body
- Totally wet furnace
- Frontal access to the combustion chamber for easy cleaning
- Possibility of low-temperature operation
- Each section is hydraulically tested at 10 bar
- Assembled body is hydraulically tested at 8 bar
- Highly resistant to condensation
- Production cycle certified according to ISO 9002 Standards
  

Delivery Composition

Delivery include :
- complete boiler body
- painted steel sheet metal case
- Glass wool insulation
- control panel

Dimensions And Weight

B40

6

7

8

9

10

11

12

Height

H  mm

1.100

1.100

1.100

1.100

1.100

1.100

1.100

Width

L  mm

668

668

668

668

668

668

668

Depth

P  mm

885

1.005

1.130

1.250

1.370

1.495

1.615

Weight

Kg

410

465

520

575

630

685

740